Drawings to send
- Mechanical floor plans
- Equipment and diffuser schedules
- Mechanical specifications
Commercial HVAC takeoff keeps supply, return, exhaust, and outside air apart. Linear feet of duct are not sheet-metal area, and sheet-metal area is not equipment.

Send mechanical plans, equipment schedules, and the specification section that states the duct measurement basis.
HVAC scope is typically turned around in 24–48 hours for most estimates. The fee is typically $150–$1,000 per estimate and depends on project size and scope.
A straight rectangular run can be recorded as LF by size or as nominal surface. For an 18 by 12 inch duct, the four-sided perimeter is 60 inches, or 5 feet. A 24-foot run is 120 SF of nominal surface before fittings, seams, and waste. Diffusers and equipment are counted from schedules by tag. Insulation, controls, test-and-balance, and rigging are separate lines. The Excel file labels the measurement basis so a square-foot rate is not applied to a linear-foot quantity.
These rows show how a commercial workbook can separate units. They are teaching lines, not a client bid and not a price.
| Line item | Unit or basis | Drawing reference | Review note |
|---|---|---|---|
| Straight duct surface | SF | Duct plan | Nominal four sides before fittings |
| Duct by size | LF | Duct plan | Use this when the spec prices by length |
| Air devices | EA | Diffuser schedule | Reconcile tags to the plan |
| Equipment | EA | Equipment schedule | Insulation and controls excluded unless specified |
A related teaching file is available: HVAC takeoff worksheet. It is not a bid deliverable.
Trace supply, return, exhaust and outside-air systems separately. Duct quantities need dimensions and a stated basis such as LF by size or developed surface SF; reconcile air devices and equipment tags to schedules.
Insulation, controls, testing and balancing, startup and rigging are separate scope decisions. LF of duct cannot be converted into sheet-metal weight without geometry and material thickness.
Illustrative duct run: 24 LF of 18 x 12 in duct is a linear measurement, not duct surface area. For four-sided straight duct, nominal sheet-metal area is 24 x (2 x 18 + 2 x 12) / 12 = 120 SF, before fittings and allowances.
No. That figure is nominal straight-duct surface only. Elbows, transitions, and reinforcement need their own basis from the specification.
Only when the documents say so. A controls contractor and a sheet-metal contractor can both touch the same air handler.
Match tags on the plan to the schedule. A count of symbols is not enough when the schedule lists a different model or quantity.
Inclusions, exclusions, and whether this trade is in your package are confirmed in the project quote. This page does not certify design or code compliance. PlanSwift and Bluebeam are named only as tools used in the industry.